1
Enquiry
direct order
✓
Quote
5
Look after it
not yet
Status
Dispatched — serial FBA-26-0407
Cost posted to HAC-J2611; inter-company invoice FBA-23104 raised.
✓
Released
✓
Plasma cutting
✓
Fabrication
✓
Balancing
✓
Assembly
✓
Test run
✓
Ready to dispatch
✓
Dispatched
Fan specificationDispatched
- Customer
- Harvey Air Conditioning (inter-company) · order HAC-J2611 / EF-14-01
- For contract
- HAC-J2611 Parramatta Square 6 — Levels 14–16 fitout
- Model
- ILC-450 — In-line Centrifugal, 450 mm impeller
- Duty
- 1,200 l/s @ 380 Pa static
- Drive
- 0.75 kW 4-pole WEG W22 · Arr 9 in-line
- Handing
- CW 0°
- Finish
- Prime coat
- Qty
- 1
- Due
- 16 Sep 2026
- Serial
- FBA-26-0407
Value
Transfer price to HAC$3,964.00 Standard cost$3,447.00 Materials (BOM at stores cost)$2,202.80 Shop hours (est.)13.4 h Margin$517 · 13%
Dispatched 16 Sep 2026 · 14:30
Bill of materialsissued from stores on dispatch
| Part | Description | Bin | Qty | On hand | Allocated (all WOs) | Cost | Status |
|---|---|---|---|---|---|---|---|
| BRG-SNL511 | SKF SNL 511 plummer block + 22211 bearing | Store 2-B | 2 ea | 14 | 0 | $368 | Issued |
| PUL-SPA | Taper-lock pulley SPA + bush | Store 2-C | 2 ea | 45 | 26 | $172 | Issued |
| VB-SPA | V-belt SPA wedge | Store 2-D | 2 ea | 72 | 26 | $38 | Issued |
| FAST-KIT | Fastener kit — HT bolts, nuts, washers | Store 1-A | 1 kit | 50 | 26 | $34 | Issued |
| GRD-BELT | Belt & shaft guard (mesh) | Rack D3 | 1 ea | 39 | 23 | $94 | Issued |
| GRD-INLET | Inlet guard (mesh) | Rack D3 | 1 ea | 52 | 34 | $56 | Issued |
| CONE-SW | Spun inlet cone — single inlet | Rack D1 | 1 ea | 25 | 18 | $168 | Issued |
| MOT-0.75 | WEG W22 IE3 0.75 kW 4-pole TEFC | Motor bay 1 | 1 ea | 3 | 0 | $347 | Issued |
| AVM-SET | Anti-vibration mount set (4) | Store 2-E | 1 set | 36 | 26 | $118 | Issued |
| PNT-PRM | Zinc phosphate primer | Paint store | 2 L | 125 | 82 | $33 | Issued |
| SH-40 | EN8 shaft bar Ø40 | Rack C1 | 1.4 m | 14 | 0 | $73 | Issued |
| PL-3 | HR plate 3mm 2400×1200 | Rack A1 | 1 sheet | 72 | 45 | $148 | Issued |
| PL-5 | HR plate 5mm 2400×1200 | Rack A2 | 2 sheet | 44 | 26 | $492 | Issued |
| CH-100 | PFC channel 100×50 — 1m | Rack B1 | 2 m | 124 | 67 | $62 | Issued |
Fan & Blower Company of Australia Pty Ltd
Cnr Macarthur & Fennell Sts, Parramatta NSW 2150 · (02) 9630 5100 · sales@fanblower.com.au
ABN 17 000 617 245
Test certificate
FBA-26-0407
Works order WO-26115
Date 13 Sep 2026
Customer order HAC-J2611 / EF-14-01
For
Harvey Air Conditioning — HAC-J2611
Parramatta Square 6 — Levels 14–16 fitout
Parramatta NSW
| Model | ILC-450 — In-line Centrifugal 450 backward inclined |
| Quantity | 1 |
| Duty | 1,200 l/s @ 380 Pa static |
| Motor | 0.75 kW 4-pole TEFC IE3 |
| Arrangement / handing | Arr 9 in-line · CW 0° |
| Finish | Prime coat |
| Serial | FBA-26-0407 |
Test run results — Pass
Test speed
1875 rpmBalance grade
G2.5Vibration (bearing housing)
2 mm/s RMSMotor current
1.4 ASound @ 1 m
86 dB(A)Tested by
Mick Henderson · 13 Sep 2026Fan test-run at our Parramatta works. Impeller statically and dynamically balanced on our hard-bearing balancing machine.
Emails & activity · 0
No correspondence yet.