Harvey

WO-26124

1 × Series 1000 DWDI 710 aerofoil · HAC-J2627 (inter-company)
Demo 06 Oct 2026
← Works orders
Invoice FBA-23111 →
1
Enquiry
direct order
✓
Quote
5
Look after itnext
not yet
Status
Dispatched — serial FBA-26-0414
Cost posted to HAC-J2627; inter-company invoice FBA-23111 raised.
✓
Released
✓
Plasma cutting
✓
Fabrication
✓
Balancing
✓
Assembly
✓
Test run
✓
Ready to dispatch
✓
Dispatched
Fan specificationDispatched
Customer
Harvey Air Conditioning (inter-company) · order HAC-J2627 / SF-2
For contract
HAC-J2627 Burwood RSL — auditorium AHU replacement
Model
S1000-DWDI-710 — Series 1000 DWDI, 710 mm impeller
Duty
7,200 l/s @ 750 Pa static
Drive
11 kW 4-pole WEG W22 · Arr 3
Handing
ACW 0°
Finish
Prime coat
Qty
1
Due
07 Aug 2026
Serial
FBA-26-0414
Value
Transfer price to HAC$12,780.00 Standard cost$11,113.00 Materials (BOM at stores cost)$4,451.90 Shop hours (est.)32.3 h Margin$1,667 · 13%
Dispatched 07 Aug 2026 · 14:30
Bill of materialsissued from stores on dispatch
PartDescriptionBinQtyOn handAllocated (all WOs)CostStatus
BRG-SNL516SKF SNL 516 plummer block + 22216 bearingStore 2-B 2 ea1214 $692 Issued
PUL-SPATaper-lock pulley SPA + bushStore 2-C 2 ea4526 $172 Issued
VB-SPAV-belt SPA wedgeStore 2-D 3 ea7226 $57 Issued
FAST-KITFastener kit — HT bolts, nuts, washersStore 1-A 1 kit5026 $34 Issued
GRD-BELTBelt & shaft guard (mesh)Rack D3 1 ea3923 $94 Issued
GRD-INLETInlet guard (mesh)Rack D3 2 ea5234 $112 Issued
CONE-DWSpun inlet cone pair — DWDIRack D1 2 ea910 $316 Issued
MOT-11WEG W22 IE3 11 kW 4-pole TEFCMotor bay 1 1 ea20 $1,736 Issued
AVM-SETAnti-vibration mount set (4)Store 2-E 1 set3626 $118 Issued
PNT-PRMZinc phosphate primerPaint store 3 L12582 $50 Issued
SH-65EN8 shaft bar Ø65Rack C2 1.6 m10.211.7 $190 Issued
PL-3HR plate 3mm 2400×1200Rack A1 2 sheet7245 $296 Issued
PL-5HR plate 5mm 2400×1200Rack A2 2 sheet4426 $492 Issued
CH-100PFC channel 100×50 — 1mRack B1 3 m12467 $93 Issued
Fan & Blower Company of Australia
Fan & Blower Company of Australia Pty Ltd
Cnr Macarthur & Fennell Sts, Parramatta NSW 2150 · (02) 9630 5100 · sales@fanblower.com.au
ABN 17 000 617 245
Test certificate
FBA-26-0414
Works order WO-26124
Date 04 Aug 2026
Customer order HAC-J2627 / SF-2
For
Harvey Air Conditioning — HAC-J2627
Burwood RSL — auditorium AHU replacement
Parramatta NSW
ModelS1000-DWDI-710 — Series 1000 DWDI 710 aerofoil
Quantity1
Duty7,200 l/s @ 750 Pa static
Motor11 kW 4-pole TEFC IE3
Arrangement / handingArr 3 · ACW 0°
FinishPrime coat
SerialFBA-26-0414
Test run results — Pass
Test speed
1185 rpm
Balance grade
G2.5
Vibration (bearing housing)
1.9 mm/s RMS
Motor current
20.9 A
Sound @ 1 m
91 dB(A)
Tested by
Mick Henderson · 04 Aug 2026
Fan test-run at our Parramatta works. Impeller statically and dynamically balanced on our hard-bearing balancing machine.